Devicenet object, Number of instances: 1 – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 367

E-2
DeviceNet Information
1503-UM054C-EN-P – June 2013
Table E.3 – Device Status
Bit No.
Status
Data Value
Bit 0
Owned
0=not owned
1=owned (Group 2 allocated to master)
Bit 1
Reserved
Always 0
Bit 2
Configured
0= not configured
1=configured
Bit 3
Reserved
Always 0
Bit 4-7
Vendor specific
All 0
Bit 8
Minor cfg fault
0=no fault
1=minor configuration fault
Bit 9
Minor device fault
0=no fault
1=minor device fault
Bit 10
Major cfg fault
0=no fault
1=major configuration fault
Bit 11
Major device fault
0=no fault
1=major device fault
Bit 12,13
Reserved
Always 0
Bit 14,15
Reserved
Always 0
Note:
The code build number is for internal reference only;
there shall be a corresponding frozen code package.
Table E.4 - Common Services
Service
Code
Implementation for
Service Name
Description of Service
Class Instance
0E hex
Yes
Yes
Get_Attribute_Single
Returns the contents of the
specified attribute.
10 hex
No
Yes
Set_Attribute_Single
Set the heartbeat value.
05 hex
No
Yes
Reset
Invokes the Reset service
for the device.
DeviceNet Object
Table E.5 - Class Attributes
Attribute ID
Access
Rule
Name
DeviceNet
Data Type
Data Value
1
Get
Revision
UINT
2
Number of Instances: 1