Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 120

Advertising
background image

Configuration/Programming 8-15

1503-UM054C-EN-P – June 2013


Updating the IntelliVAC Plus using Control Flash

In order to update the firmware of the IntelliVAC Plus module using

DeviceNet you will need the following:

1. Personal computer equipped with a DeviceNet interface such as

a 1784-PCD or 1770-KFD

2. RS-Links Software

3. Control Flash Software

4. A functioning device net network including 24VDC DeviceNet

power supply.

Flashing FW using Control Flash

Browse DeviceNet network using RSLinx to ensure that the

network is communicating correctly and the IntelliVAC Plus is

found

Figure 8.11 - View IntelliVAC Plus using RSLinx


Once you have verified that your network is functioning correctly

by finding the IntelliVAC Plus open Control flash software

Select “Next” at the opening screen, you will then be prompted to

locate the firmware file to be flashed. Select the “Browse” option

and locate the firmware file which has been supplied by Rockwell

technical support. Once this is complete select “Next”

A browser window similar to RSLinx will appear select the

IntelliVAC Plus then select “OK”