Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 191

Advertising
background image

B-16

Parameters

1503-UM054C-EN-P – June 2013

Contactor Relay Status for IntelliVAC Base Unit #1
[IB 1 Contactor Status Relay Status]

Parameter Number:

26,21,16,11,6.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-1-6

Group:

Control

Units:

-

Minimum Value:

0 = Open

Maximum Value:

1 = Closed

Default Value:

0

This parameter allows the user to view the status of the Contactor

Status relay for the IntelliVAC Basic Module #1. An Open refers to

the Contactor Status relay contacts being in an Open state. A Closed

status refers to the Contactor Status relay contacts being in a Closed

state. See the Electrical Specifications section in Table 1.A for the

Contactor Status relay contact ratings.


Contactor Relay Status for IntelliVAC Base Unit #2
[IB 2 Contactor Status Relay Status]

Parameter Number:

27,22,17,12,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-2-6

Group:

Control

Units:

-

Minimum Value:

0 = Open

Maximum Value:

1 = Closed

Default Value:

0

This parameter allows the user to view the status of the Contactor

Status relay for the IntelliVAC Basic Module #2. An Open refers to

the Contactor Status relay contacts being in an Open state. A Closed

status refers to the Contactor Status relay contacts being in a Closed

state. See the Electrical Specifications section in Table 1.A for the

Contactor Status relay contact ratings.