Parameters

1503-UM054C-EN-P – June 2013


Drop Out Time Setting for IB4
[IB 4 Drop Out Time]
Parameter Number:

116,100,_,_,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-4-13

Group:

Configuration

Units:

milliseconds

Minimum Value:

50

Maximum Value:

240

Default Value:

50

This parameter allows the user to view and set the Drop Out Time

setting for the IB4 module. The Drop Out Time is the time required

from the moment that an Open or Trip command is issued to the time

that the Contactor Auxiliary Status contact, on IB4, closes, to

indicate that the contactor has opened. See Contactor Drop Out

Time in Chapter 8 and Table 8.B.


Drop Out Time Setting for IB5
[IB 5 Drop Out Time]

Parameter Number:

117,_,_,_,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-5-13

Group:

Configuration

Units:

milliseconds

Minimum Value:

50

Maximum Value:

240

Default Value:

50

This parameter allows the user to view and set the Drop Out Time

setting for the IB5 module. The Drop Out Time is the time required

from the moment that an Open or Trip command is issued to the time

that the Contactor Auxiliary Status contact, on IB5, closes, to

indicate that the contactor has opened. See Contactor Drop Out

Time in Chapter 8 and Table 8.B.