B-62

Parameters

1503-UM054C-EN-P – June 2013


Learn Mode Setting From IB5
[IB 5 Learn Mode Setting]
Parameter Number:

112,_,_,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-5-17

Group:

Configuration

Units:

-

Minimum Value:

0 = Off

Maximum Value:

1 = On

Default Value:

0

This parameter allows the user to view the status of the Learn Mode

setting for the IB5 module. If it is Off, then the IB5 contactor will

not try to determine the type of contactor that it is connected to. If it

is On, then the IB5 contactor will try to determine the type of

contactor that it is connected to. This feature is not functional on the

Rev 1.01 firmware release

.


Drop Out Time Setting for IB1
[IB 1 Drop Out Time]

Parameter Number:

113,97,81,65,48.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-1-13

Group:

Configuration

Units:

milliseconds

Minimum Value:

50

Maximum Value:

240

Default Value:

50

This parameter allows the user to view and set the Drop Out Time

setting for the IB1 module. The Drop Out Time is the time required

from the moment that an Open or Trip command is issued to the time

that the Contactor Auxiliary Status contact, on IB1, closes, to

indicate that the contactor has opened. See Contactor Drop Out

Time in Chapter 8 and Table 8.B.