Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 234

Advertising
background image

Parameters B-59

1503-UM054C-EN-P – June 2013


Power-Up Safety Setting for IB4
[IB 4 Power-Up Safety Setting]
Parameter Number:

106,92,_,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-4-16

Group:

Configuration

Units:

-

Minimum Value:

0 = Enable

Maximum Value:

1 = Disable

Default Value:

0

This parameter allows the user to view the status of the Power-Up

Safety setting for the IB4 module. If it is enabled then the IB4

contactor will not close the contactor if the unit powers up with a

Close command present. If it is disabled then the IB4 contactor will

close the contactor if the unit powers up with a Close command

present. See Power-up Safety in Chapter 8 and Table 8.F.


Power-Up Safety Setting for IB5
[IB 5 Power-Up Safety Setting]

Parameter Number:

107,_,_,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-5-16

Group:

Configuration

Units:

-

Minimum Value:

0 = Enable

Maximum Value:

1 = Disable

Default Value:

0

This parameter allows the user to view the status of the Power-Up

Safety setting for the IB5 module. If it is enabled then the IB5

contactor will not close the contactor if the unit powers up with a

Close command present. If it is disabled then the IB5 contactor will

close the contactor if the unit powers up with a Close command

present. See Power-up Safety in Chapter 8 and Table 8.F.