B-4

Parameters

1503-UM054C-EN-P – June 2013

Auxiliary Input Status from IntelliVAC Base Unit #2
[IB 2 Module Aux. Status]
Parameter Number:

2,2,2,2,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-2-1

Group:

Control

Units:

-

Minimum Value:

0 = Closed

Maximum Value:

1 = Open

Default Value:

0

This parameter allows the user to view the status of the contactor

Auxiliary input from the IntelliVAC Basic Module #2. A Closed

status refers to the contactor Auxiliary input having no input voltage

which indicates that the contactor is Closed. An Open status refers

to the contactor Auxiliary input having a valid input voltage which

indicates that the contactor is Open. See the Electrical Specifications

section in Table 1.A for the voltage level for a valid Closed and

Open input.


Auxiliary Input Status from IntelliVAC Base Unit #3
[IB 3 Module Aux. Status]
Parameter Number:

3,3,3,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-3-1

Group:

Control

Units:

-

Minimum Value:

0 = Closed

Maximum Value:

1 = Open

Default Value:

0

This parameter allows the user to view the status of the contactor

Auxiliary input from the IntelliVAC Basic Module #3. A Closed

status refers to the contactor Auxiliary input having no input voltage

which indicates that the contactor is Closed. An Open status refers to

the contactor Auxiliary input having a valid input voltage which

indicates that the contactor is Open. See the Electrical Specifications

section in Table 1.A for the voltage level for a valid Closed and

Open input.