DeviceNet Information E-17

1503-UM054C-EN-P – June 2013

Table E.29 – DeviceLogix Data Table Layout (cont.)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

NUMBER_OF_HARDWARE_INPUT_FAULT_BYTES (C8-FE) = 7 bytes

Byte 25

IB1– Long

contactor

drop out

time

IB1 –

Contactor

drop out

during hold

IB1 –

Contactor

fails to pick

up

IB1 – Power

up with

contactor

close (EH

only)

IB1–

Mechanical

Latch Fail to

Trip

IB1– Invalid

Command

Present

IB1 – Healthy

Module &

Contactor close

IB1 – Healthy

Module &

Contactor open

Byte 26

IB2– Power

up with

contactor

close

(EH only)

IB2 –

Mechanical

Latch Fail to

Trip

IB2 –Invalid

Command

Present

IB2 – Healthy

Module &

Contactor

Close

IB2 – Healthy

Module &

Contactor

Open

IB1 –

Undervoltage

with close

command

present

IB1 – Power up

w/ Invalid DIP

Config.

IB1 – CPU

Malfunction

Byte 27

IB3 –

Healthy

Module &

Contactor

Close

IB3 –

Healthy

Module &

Contactor

Open

IB2 –

Undervoltag

e with close

command

present

IB2 – Power

up w/ Invalid

DIP Config.

IB2 – CPU

Malfunction

IB2 – Long

contactor

drop out time

IB2 – Contactor

drop out during

hold

IB2 – Contactor

fails to pick up

Byte 28

IB3 –

Power up

w/ Invalid

DIP Config.

IB3 – CPU

Malfunction

IB3 – Long

contactor

drop out

time

IB3 –

Contactor

Drop Out

during hold

IB3 –

Contactor

fails to pick

up

IB3 – Power

up with

Contactor

close (EH

only)

IB3 –

Mechanical

Latch Fail to

Trip

IB3 – Invalid

Command

Present

Byte 29

IB4 –

Contactor

drop out

during hold

IB4 –

Contactor

fails to pick

up

IB4 – Power

up with

contactor

close

(EH only)

IB4 –

Mechanical

Latch fail to

trip

IB4 – Invalid

Command

Present

IB4 – Healthy

Module &

Contactor

Close

IB4 – Healthy

Module &

Contactor open

IB3 –

Undervoltage

with close

command

present

Byte 30

IB5 –

Mechanical

Latch Fail

to Rip

IB5 –

Invalid

Command

Present

IB5 –

Healthy

Module &

Contactor

close

IB5 – Healthy

Module &

Contactor

open

IB4 –

Undervoltage

with close

command

present

IB4 – Power

up w/ Invalid

DIP Config.

IB4 – CPU

Malfunction

IB4 –- Long

contactor drop

out time

Byte 31

XXX

This bit can

not be used

IB5 –

Undervoltage

with close

command

present

IB5 – Power

up w/ Invalid

DIP Config.

IB5 – CPU

Malfunction

IB5 – Long

contactor

drop out time

IB5 – Invalid

Command

Present

IB5 – Contactor

fails to pick up

IB5 – Power up

with Contactor

close (EH only)

Note:

*: S tart Ready Status is the all status of Jog Restart

**: Fault Bit is the IE and IB fault status