Description of Features 4-41

1503-UM054C-EN-P – June 2013

IE Determining Network Baud Rate

The DeviceNet status LED is flashing Green.

On-Line but Not Allocated to Master

The DeviceNet status LED is flashing Green.

Normal Operation & Allocated to a Master

This is a Normal condition and indicates that the IntelliVAC Plus is

on-line and has connections in the established state. As a UCMM

capable device it means that it has one or more established

connections.

The DeviceNet status LED is solid Green.

I/O Connection Timed Out

This is a Warning condition and indicates that the IntelliVAC Plus

has one or more I/O connections in a timed-out state.

The DeviceNet status LED is flashing Red.


Bus Off or Duplicate DeviceNet Address Detected or Invalid Baud

Rate

This is a Fault condition and indicates that the IntelliVAC Plus has

failed communication. The device has detected an error that has

rendered it incapable of communicating on the network. This may

be due to one of the following conditions: i) DeviceNet failure

during power-up ii) duplicate DeviceNet address detected and iii)

Invalid baud rate).

The DeviceNet status LED is solid Red.


Module Status (DeviceNet)

As per the ODVA rules the LED used for IE Faults/Warnings

(Module Status LED) will also be used for DeviceNet Module

Status. The function of this status LED is already defined in Table

4.F for the IE module. However, this IE module status LED will

also have a combined usage along with the DeviceNet Module

Status. The functionality of the DeviceNet Module Status LED is

shown in Table 4.I.

Network Status

(DeviceNet)

(cont.)