Output (consumed) assembly and layout, Ib outa=close coil command, Ib outb=open coil command – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 372

DeviceNet Information E-7
1503-UM054C-EN-P – June 2013
Output (Consumed) Assembly and Layout
Output assembly instances attribute and format (produced by DeviceNet Master,
consumed by IE)
IB OutA=close coil command
IB OutB=open coil command
Table E.14 – Output (Consumed) Assembly Instance – Commands
Instance 1, 3 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
---
---
---
---
---
---
IE-Out B
IE-Out A
1
CNB7
CNB6
CNB5
CNB4
CNB3
CNB2
CNB1
CNB0
2
CNB15
/Net Jog
CNB14
/Net REV
CNB13
/Net FWD
CNB12
/Net Stop
CNB11
/Net Start
CNB10
CNB9
CNB8
Table E.15 – Output (Consumed) Assembly Instance – Outputs
Instance 2, 1 byte
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
---
---
---
---
---
---
IE-Out B
IE-Out A
Table E.16 – Output (Consumed) Assembly Instance – Commands
Instance 3, 2 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
CNB7
CNB6
CNB5
CNB4
CNB3
CNB2
CNB1
CNB0
1
CNB15
/Net Jog
CNB14
/Net REV
CNB13
/Net FWD
CNB12
/Net Stop
CNB11
/Net Start
CNB10
CNB9
CNB8