Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 197

B-22
Parameters
1503-UM054C-EN-P – June 2013
Close Coil Current for IntelliVAC Base Unit #3
[IB 3 Close Current]
Parameter Number:
38,31,24,_,_.
Access rule:
Get
Data Type:
FLOAT
Object Mapping:
0x384-3-8
Group:
Control
Units:
Amperes
Minimum Value:
00.000A
Maximum Value:
99.999A
Default Value:
00.000A
This parameter allows the user to view the average value for the
Close coil current on the IntelliVAC Basic Module #3. This coil
current is only valid for the first 200mS after the Close coil is
energized.
Close Coil Current for IntelliVAC Base Unit #4
[IB 4 Close Current]
Parameter Number:
39,32,_,_,_.
Access rule:
Get
Data Type:
FLOAT
Object Mapping:
0x384-4-8
Group:
Control
Units:
Amperes
Minimum Value:
00.000A
Maximum Value:
99.999
Default Value:
00.000A
This parameter allows the user to view the average value for the
Close coil current on the IntelliVAC Basic Module #4. This coil
current is only valid for the first 200mS after the Close coil is
energized.