Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 355

Advertising
background image

B-180

Parameters

1503-UM054C-EN-P – June 2013

Termination Resistor Installed in IB5
[IB5 Termination Resistor]
Parameter Number:

344,_,_,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-5-63

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of the MC Termination

Resistor installation on IB5. If this bit is ‘0’, then the MC Termination

Resistor is not installed on the IB5 unit. If this bit is ‘1’, then the MC

Termination Resistor is installed on the IB5 unit. For the MC system to

have the correct Termination Resistor installed, only the last MC unit in

the MC system must have its resistor turned on.

Status Word for the IE [IE Status Word]

Parameter Number:

345,284,223,162,100.

Access rule:

Get/Set

Data Type:

WORD

Object Mapping:

0xB4-1-128

Group:

Diagnostics

Units:

-

Minimum Value:

0

Maximum Value:

0xFFFF

Default Value:

0

This parameter allows the user to view the IE Status Word.

If a bit is

‘0’ then the fault or warning is not present. If a bit is a ‘1’ then the

fault or warning is present. See Table 4.F and Table 4.J in Chapter 4

for a detailed description of each of the IE Status Word bits.

Table B.44 – Status Word for IE

Bit

Enum Text

Description

0

System locked

System locked due to repeated fault

1

Line under-voltage

Line under-voltage

2

Line over-voltage

Line over-voltage

3

Altitude setting warning

Altitude settings inconsistent in MC system

4

RTC failure

RTC failure

5

DNet power loss

DeviceNet power loss

6

IB5 not responding

IB5 not responding on RS485

7

IB4 not responding

IB4 not responding on RS485

8

IB3 not responding

IB3 not responding on RS485

9

IB2 not responding

IB2 not responding on RS485

10 IB1 not responding

IB1 not responding on RS485

11 unused

unused

12 RS485 incorrect address

RS485 incorrect address

13 RS485 communication fault

RS485 communication fault

14 unused

unused

15 unused

unused