Delay Restart Time for IB1
[IB 1 Delay Restart Time]

Parameter Number:

138,117,96,75,53.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-1-19

Group:

Configuration

Units:

Seconds

Minimum Value:

6

Maximum Value:

3600

Default Value:

12

This parameter allows the user to view and set the Delay Restart

Time between successive Open/Trip and Close commands for

contactor IB1. This sets a maximum repetition time for the cycling

of the contactor. It can also be used to prevent rapid restating of the

motor. See Delayed Restart in Chapter 4 for a more detailed

description of this feature.