Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 354

Advertising
background image

Parameters B-179

1503-UM054C-EN-P – June 2013

Termination Resistor Installed in IB3
[IB3 Termination Resistor]

Parameter Number:

342,282,222,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-3-63

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of the MC

Termination Resistor installation on IB3. If this bit is ‘0’, then the

MC Termination Resistor is not installed on the IB3 unit. If this bit

is ‘1’, then the MC Termination Resistor is installed on the IB3 unit.

For the MC system to have the correct Termination Resistor installed,

only the last MC unit in the MC system must have its resistor turned

on.

Termination Resistor Installed in IB4
[IB4 Termination Resistor]

Parameter Number:

343,282,_,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-4-63

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of the MC

Termination Resistor installation on IB4. If this bit is ‘0’, then the

MC Termination Resistor is not installed on the IB4 unit. If this bit

is ‘1’, then the MC Termination Resistor is installed on the IB4 unit.

For the MC system to have the correct Termination Resistor installed,

only the last MC unit in the MC system must have its resistor turned

on.