Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 244

Parameters B-69
1503-UM054C-EN-P – June 2013
Contactor Pick Up Time for IB3
[IB 3 Pick Up Time]
Parameter Number:
125,107,89,_,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-3-18
Group:
Configuration
Units:
mSeconds
Minimum Value:
0
Maximum Value:
255
Default Value:
0
This parameter allows the user to view the Pick Up Time for the IB3
contactor. The Pick Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB3 opens, indicating that the contactor is closed.
Contactor Pick Up Time for IB4
[IB 4 Pick Up Time]
Parameter Number:
126,108,_,_,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-4-18
Group:
Configuration
Units:
mSeconds
Minimum Value:
0
Maximum Value:
255
Default Value:
0
This parameter allows the user to view the Pick Up Time for the IB4
contactor. The Pick Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB4 opens, indicating that the contactor is closed.