7-6

Communications

1503-UM054C-EN-P – June 2013

Mask HIM/PC

Logic mask 3 is considered a test and diagnostic state. As such if

network communication is lost when operating with logic mask 3

selected the unit will always reset regardless of the selected loss of

communication state parameter.


Note:

Logic mask 0 is not affected by a loss of communication

regardless of whether the “HOLD STATE” or “RESET

STATE” options are selected since this logic mask accepts

commands only from local HW I/O.

Multi-Contactor Control Bus (MC)

An MC system is capable of controlling up to four (4) IntelliVAC

MC units with one (1) IntelliVAC Plus unit being the main

controller. In an MC system the address of each of the IntelliVAC

MC units must be correct so that there will be the correct number of

units in the particular MC configuration with no duplicate addresses

selected. The address is set by DIP switches on the MC module that

is attached to each IB unit in the IntelliVAC MC unit. The IB unit

that is attached to the IE unit in an IntelliVAC Plus will always be

address 1 and the IE unit will always be address 0. See Table 8.H for

a description of the DIP switch settings. The 7-segment LED display

on the IntelliVAC Plus unit, will display address 1 and not 0 (the

address of the IE unit is not displayed). Other IntelliVAC MC units

will display the address selected by the DIP switches. If the

addresses selected are not in the range of 2 to 5, then the display will

remain blank.