Parameters B-33

1503-UM054C-EN-P – June 2013

DC Bus Voltage for IntelliVAC Base Unit #5
[IB 5 DC Bus Voltage]

Parameter Number:

60,_,_,_,_.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x384-5-12

Group:

Control

Units:

Volts

Minimum Value:

00.000V

Maximum Value:

399.999V

Default Value:

00.000V

This parameter allows the user to view the DC value for the DC Bus

voltage on the IntelliVAC Basic Module #5.


Enhanced Module Hardware Input Status
[IE Hardware Inputs]

Parameter Number:

61,49,37,25,13.

Access rule:

Get

Data Type:

BYTE

Object Mapping:

0x4-11-3

Group:

Control

Units:

-

Minimum Value:

-

Maximum Value:

-

Default Value:

None

This parameter allows the user to view the status of the eight (8)

hardware inputs. Each bit position of the parameter defines the state

of one of the hardware inputs. If the voltage to an input is lower than

the maximum required, as defined in the Electrical Specifications in

Table 1.A, then the corresponding bit will indicate a ‘0’. If the

voltage to an input exceeds the minimum required, as defined in the

Electrical Specifications in Table 1.A, then the corresponding bit will

indicate a ‘1’.

Table B.4 – Enhanced Module Hardware Input States

Bit

Enum Text

Description

0

Bit 0: DLX Input 1

Status of DeviceLogix Input #1

1

Bit 1: DLX Input 2

Status of DeviceLogix Input #2

2

Bit 2: DLX Input 3

Status of DeviceLogix Input #3

3

Bit 3: DLX Input 4

Status of DeviceLogix Input #4

4

Bit 4: DLX Input 5

Status of DeviceLogix Input #5

5

Bit 5: DLX Input 6

Status of DeviceLogix Input #6

6

Bit 6: DLX Input 7

Status of DeviceLogix Input #7

7

Bit 7: DLX Input 8

Status of DeviceLogix Input #8