Parameters B-173

1503-UM054C-EN-P – June 2013

Status Word for IB1 [IB 1 Status Word]

Parameter Number:

335,276,217,158,98.

Access rule:

Get

Data Type:

WORD

Object Mapping:

0x384-1-62

Group:

Diagnostics

Units:

-

Minimum Value:

0

Maximum Value:

0xFFFF

Default Value:

0

This parameter allows the user to view the IB1 Status Word.

If a bit

is ‘0’ then the fault or warning is not present. If a bit is a ‘1’ then the

fault or warning is present.

Table B.39 – Status Word for IB1

Bit

Enum Text

Description

0

Bit 0: unused

unused

1

Bit 1: unused

unused

2

Bit 2: unused

unused

3

Bit 3: Power Up with Contactors Closed

Power Up with Contactor Closed IB1

4

Bit 4: Open Coil Open

Trip Coil Open on IB1

5

Bit 5: Close Coil Open

Close Coil Open on IB1

6

Bit 6: Power Up with Invalid DIPs

Power Up with Invalid DIPs on IB1

7

Bit 7: MC Malfunction

MC Malfunction on IB1

8

Bit 8: Drop Out During Hold

Drop Out During Hold on IB1

9

Bit 9: Contactor Fails to Drop Out

Contactor Fails to Drop Out on IB1

10

Bit 10: Power Up with Close Command

Power Up with Close Command on IB1

11

Bit 11: Long Close Time

Long Close Time on IB1

12

Bit 12: Undervoltage with Close Command Present

Undervoltage with Close Command Present on IB1

13

Bit 13: Long Drop Out Time

Long Drop Out Time on IB1

14

Bit 14: Mechanical Latch Trip Fail

Mechanical Latch Trip Fail on IB1

15

Bit 15: Invalid Command

Invalid Command on IB1