1-8

Product Description

1503-UM054C-EN-P –June 2013

Through RSNetWorx, IntelliVAC Plus firmware version can be

viewed in device general page and base module version can be

viewed in parameter page.

Series C modules use only version 2.003 application firmware.

This firmware is also compatible with the Series A and B modules.

Series D modules use only version 3.001 or 3.002 application

firmware. This firmware is not compatible with any other Series

letter modules.

Series E modules use only 4.001 or newer

firmware. This firmware is not compatible with any other Series

Letter modules.

Refer to IntelliVAC manual 1503-UM053-EN-P for part numbers

of the various series of modules. The Series Letter of the module

is printed on the label on the cover of the module, beside the part

number.


Table 1.A – Mechanical Ratings

klTemperature

Operating: 0° to 60°C ambient at the control module 
Non-Operating: -40° to 85°C

Altitude

-1000 to 5000 meters

Pollution

Pollution level II (as defined by UL 840 and IEC 60664-1)

Humidity

95% non-condensing

Shock and

Vibration

(Operational)

Shock – 15 g peak, 11 milliseconds
Vibration – 10 to 57 Hz, 0.015 inch displacement peak to peak
– 57 to 150 Hz, 2.5 g acceleration

Ambient temperature is derated at altitudes above 1,000 meters (3,300 feet).

Please refer to Table 1.C.