Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 346

Advertising
background image

Parameters B-171

1503-UM054C-EN-P – June 2013

Contactor Coil Current for IB2
[IB 2 Contactor Coil Current]

Parameter Number:

331,273,215,157,_.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x384-2-61

Group:

Diagnostics

Units:

Amperes

Minimum Value:

00.000A

Maximum Value:

99.999A

Default Value:

00.000A

This parameter allows the user to view the real time operating Coil

Current for IB2. The current will be the Hold current for Electrically

Held contactors, only, because the Close/Trip coils for Mechanically

Latched contactors are only momentary currents and are not sustained

for extended time periods. See “Coil Currents” in Chapter 4 for a

more detailed description of this feature.


Contactor Coil Current for IB3
[IB 3 Contactor Coil Current]

Parameter Number:

332,274,216,_,_.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x384-3-61

Group:

Diagnostics

Units:

Amperes

Minimum Value:

00.000A

Maximum Value:

99.999A

Default Value:

00.000A

This parameter allows the user to view the real time operating Coil

Current for IB3. The current will be the Hold current for Electrically

Held contactors, only, because the Close/Trip coils for Mechanically

Latched contactors are only momentary currents and are not sustained

for extended time periods. See “Coil Currents” in Chapter 4 for a

more detailed description of this feature.