Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 233

Advertising
background image

B-58

Parameters

1503-UM054C-EN-P – June 2013


Power-Up Safety Setting for IB2
[IB 2 Power-Up Safety Setting]
Parameter Number:

104,90,76,62,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-2-16

Group:

Configuration

Units:

-

Minimum Value:

0 = Enable

Maximum Value:

1 = Disable

Default Value:

0

This parameter allows the user to view the status of the Power-Up

Safety setting for the IB2 module. If it is enabled then the IB2

contactor will not close the contactor if the unit powers up with a

Close command present. If it is disabled then the IB2 contactor will

close the contactor if the unit powers up with a Close command

present. See Power-up Safety in Chapter 8 and Table 8.F.


Power-Up Safety Setting for IB3
[IB 3 Power-Up Safety Setting]

Parameter Number:

105,91,77,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-3-16

Group:

Configuration

Units:

-

Minimum Value:

0 = Enable

Maximum Value:

1 = Disable

Default Value:

0

This parameter allows the user to view the status of the Power-Up

Safety setting for the IB3 module. If it is enabled then the IB3

contactor will not close the contactor if the unit powers up with a

Close command present. If it is disabled then the IB3 contactor will

close the contactor if the unit powers up with a Close command

present. See Power-up Safety in Chapter 8 and Table 8.F.