B-74

Parameters

1503-UM054C-EN-P – June 2013


TDUV Time Setting for IB2
[IB 2 TDUV Time]
Parameter Number:

134,114,94,74,_.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-2-50

Group:

Configuration

Units:

Seconds error in EDS file

Minimum Value:

0.2

Maximum Value:

2.0

Default Value:

0.2

This parameter allows the user to view and set the Time Delay

Undervoltage setting for the IB2 module. The Time Delay

Undervoltage setting is the time allowed for contactor IB2 to remain

operational when the mains input voltage goes below the minimum

operating voltage (see Electrical Specifications section for both

Close and Hold modes). See TDUV Programmability in Chapter 4

for a detailed description of this feature.


TDUV Time Setting for IB3
[IB 3 TDUV Time]

Parameter Number:

135,115,95,_,_.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-3-50

Group:

Configuration

Units:

Seconds error in EDS file

Minimum Value:

0.2

Maximum Value:

2.0

Default Value:

0.2

This parameter allows the user to view and set the Time Delay

Undervoltage setting for the IB3 module. The Time Delay

Undervoltage setting is the time allowed for contactor IB3 to remain

operational when the mains input voltage goes below the minimum

operating voltage (see Electrical Specifications section for both

Close and Hold modes). See TDUV Programmability in Chapter 4

for a detailed description of this feature.