Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 242

Advertising
background image

Parameters B-67

1503-UM054C-EN-P – June 2013

Drop Out Time Setting From IB4 DIP Switches
[IB 4 Drop Out Time DIP Setting]

Parameter Number:

121,104,_,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-4-49

Group:

Configuration

Units:

see table

Minimum Value:

0

Maximum Value:

7

Default Value:

0

This parameter allows the user to view the Drop Out Time Setting

set from the IB4 DIP switches. The Drop Out Time is initially set by

the IB4 DIP switches but can be over-ridden by Parameter #116 after

which time the original IB4 DIP switch settings will no longer be used.

Table B.26 – Drop Out Time Settings From IB4 DIP Switches

Value

Enum Text

Description

0

50 ms

50 ms from IB4 DIP switches

1

75 ms

75 ms from IB4 DIP switches

2

100 ms

100 ms from IB4 DIP switches

3

130 ms

130 ms from IB4 DIP switches

4

150 ms

150 ms from IB4 DIP switches

5

175 ms

175 ms from IB4 DIP switches

6

200 ms

200 ms from IB4 DIP switches

7

240 ms

240 ms from IB4 DIP switches

Note:

The drop off time would be 6mS longer if the close command

is applied on IB.


Drop Out Time Setting From IB5 DIP Switches
[IB 5 Drop Out Time DIP Setting]

Parameter Number:

122,_,_,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-5-49

Group:

Configuration

Units:

see table

Minimum Value:

0

Maximum Value:

7

Default Value:

0

This parameter allows the user to view the Drop Out Time Setting

set from the IB5 DIP switches. The Drop Out Time is initially set by

the IB5 DIP switches but can be over-ridden by Parameter #117 after

which time the original IB5 DIP switch settings will no longer be used.