Wiring (MC) 6-3
1503-UM054C-EN-P – June 2013
Figure 6.2 – Wiring Diagram for Full Voltage Reversing
Configuration Required:
•
Gate #34 Off Delay Timer Reverse Contactor
•
Gate #32 Off Delay Timer Forward Contactor
Gates # 32 and 34 are the close command disable timers for the respective contactors,
typically these timers are set to an equal value.
The purpose of these timers is to allow a motor turning in the forward direction a pre
determined amount of time to come to a stop before the reverse contactor can be closed
and vice versa. Preset Value: 10 Seconds