Wiring (MC) 6-3

1503-UM054C-EN-P – June 2013

Figure 6.2 – Wiring Diagram for Full Voltage Reversing

Configuration Required:

Gate #34 Off Delay Timer Reverse Contactor

Gate #32 Off Delay Timer Forward Contactor

Gates # 32 and 34 are the close command disable timers for the respective contactors,

typically these timers are set to an equal value.

The purpose of these timers is to allow a motor turning in the forward direction a pre

determined amount of time to come to a stop before the reverse contactor can be closed

and vice versa. Preset Value: 10 Seconds