Parameter Object

The parameter object and parameter object are all for mainly for 193-HIM to

get online parameters.

Table E.10 - Class Attributes

Attribute

ID

Access

Rule

Name

DeviceNet Data Type

Data Value

1

Get

Revision

UINT

3

2

Get

Max instance

UINT

24

8

Get

Parameter

Class

Descriptor

WORD

0b

Bit 0: Supports Parameter

Instances

Bit 1: Supports Full Attributes
Bit 2: Must do non-volatile

storage save command

Bit 3: Params are stored in Non-

Volatile storage

9

Get

Configuration

Assembly

Instance

UINT

0

There is a set of instances reserved for IE plus module. The following instance

attributes are implemented for all parameter attributes:

Table E.11 - Class Instances

Attribute

ID

Access

Rule

Attribute Name

Data Type

1

Get/Set

Value

Specified in descriptor

2

Get

Link path size

USINT

3

Get

Link path

Array of:

Byte

EPATH

4

Get

Descriptor

WORD

5

Get

Data type

EPATH

6

Get

Data size

USINT

7

Get

Parameter name string Short string

8

Get

Unit string

Short string

9

Get

Help string

Short string

10

Get

Min value

Specified in descriptor

11

Get

Max value

Specified in descriptor

12

Get

Default value

Specified in descriptor

13

Get

Scaling multiplier

UINT

14

Get

Scaling divisor

UINT

15

Get

Scaling base

UINT

16

Get

Scaling offset

INT

17

Get

Multiplier Link

UINT

18

Get

Divisor Link

UINT

19

Get

Base Link

UINT

20

Get

Offset Link

UINT

21

Get

Decimal Precision

USINT