Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 377

Advertising
background image

E-12

DeviceNet Information

1503-UM054C-EN-P – June 2013

Table E.25 - Instance Attribute

Parameter

No.

Control Parameter

Access

Rule

Type

Description

NV

CCV

1

AUX Status

Get

BOOL

1=open

0=close

N

N

2

CLOSE Status

Get

BOOL

0=not present

1=present

N

N

3

OPEN Status

Get

BOOL

0=not present

1=present

N

N

4

Close Coil Command

Get/Set

BOOL

1=Open

0=Close

N

N

5

Trip Coil Command

Get/Set

BOOL

1=Close

0=Open

N

N

6

Contactor Relay Status

Get

BOOL

0=open

1=close

N

N

7

Module Relay Status

Get

BOOL

0=open

1=close

N

N

8

Close Current

Get

LONG INT* 0~xx.xxx A

N

N

9

Hold Current

Get

LONG INT* 0~xx .xxx A

N

N

10

Trip Current

Get

LONG INT* 0~xx.xxx A

N

N

11

Line Voltage

Get

LONG INT* 0~xx.xxx V

N

N

12

DC Bus Voltage

Get

LONG INT* 0~xx.xxx V

N

N

13

Drop-out Time

(from IB or IE)

Get/Set

USINT

50~240 ms

Y

Y

14

Contactor Type (from IB)

Get

USINT

0=400A Mech. Latch

1=400A Elec. Held

2=800A Mech. Latch

3=800A Elec. Held

4~F=TBD

N

N

15

TDUV Config (from IB)

Get/Set

BOOL

0=disable

1=enable

Y

Y

16

Power-up Safety (from IB or IE)

Get

BOOL

0=enable

1=disable

N

N

17

Learn Mode (from IB)

Get

BOOL

0=Off

1=On

N

N

18

Pick-up Time

Get

USINT

0~255 ms

N

N

19

Delay Restart Time

Get/Set

UINT

6(12) ~ 3600 Sec

Y

Y

20

Delay Restart Wait Time

Get

UINT

0 ~ 3600 Sec

N

N

21

Jog Time

Get/Set

USINT

0 ~ 30 Sec, default

12

Y

Y

22

Jog Repetition Time

Get/Set

UINT*

0 ~ 60 second,

default 6

Y

Y

23

IB Invalid Command

Get

BOOL

0=not present

1=present

N

N

24

IB Mechanical Latch Fail to Trip

Get

BOOL

0=not present

1=present

N

N

25

Contactor Fails to Pick-Up

Get

BOOL

0=not present

1=present

N

N

26

Contactor Drop-out during Hold

Get

BOOL

0=not present

1=present

N

N

27

Contactor Fails To Drop Out

Get

BOOL

0=not present

1=present

N

N

28

IB Module Not Healthy

Get

BOOL

0=not healthy

1=healthy

N

N

29

Power-up with Contactor Closed

Get

BOOL

0=not present

1=present

N

N

30

Power-up with Invalid DIP

Switch Configuration

Get

BOOL

0=not present

1=present

N

N

Advertising