Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 261

B-86
Parameters
1503-UM054C-EN-P – June 2013
Diagnostics Parameters
Invalid Command on IB1 Level
[IB 1 Invalid Command]
Parameter Number:
158,133,108,83,57.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-1-23
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of the Invalid
Command warning from the IB1 module. If the bit is ‘0’ then the
warning is not present. If the bit is ‘1’ then the warning is present.
See Invalid Command in Chapter 4 for a detailed description of this
warning.
Invalid Command on IB2 Level
[IB 2 Invalid Command]
Parameter Number:
159,134,109,84.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-2-23
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of the Invalid
Command warning from the IB2 module. If the bit is ‘0’ then the
warning is not present. If the bit is ‘1’ then the warning is present.
See Invalid Command in Chapter 4 for a detailed description of this
warning.