Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 210

Advertising
background image

Parameters B-35

1503-UM054C-EN-P – June 2013


DeviceNet Voltage [24V DeviceNet Voltage]

Parameter Number:

64,52,40,28,16.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x3-1-100

Group:

Control

Units:

Volts

Minimum Value:

0V

Maximum Value:

50.000V

Default Value:

0V

This parameter allows the user to view the DeviceNet DC voltage

level.

15V Supply Voltage from the IB [15V IB Voltage]

Parameter Number:

65,53,41,29,17.

Access rule:

Get

Data Type:

FLOAT

Object Mapping:

0x3-1-101

Group:

Control

Units:

Volts

Minimum Value:

0V

Maximum Value:

30.000V

Default Value:

0V

This parameter allows the user to view the DC supply voltage level

from the IB board.

DeviceLogix Program Selection [Preload DeviceLogix Program]

Parameter Number:

66,54,42,30,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0xB4-1-114

Group:

Control

Units:

-

Minimum Value:

0 = User customized DeviceLogix Prog.

Maximum Value:

5 = PFCC DeviceLogix Program

Default Value:

0

This parameter allows the user to view, as well as to select, the

DeviceLogix program that will be executed. There are six different

programs that can be selected. This is shown in the following

RSNetworx screen in Figure B.2.

For each of the Programs listed, a status of ‘0’ indicates that the

Program is disabled and a status of ‘1’ indicates that the Program is

enabled.