Parameters B-75

1503-UM054C-EN-P – June 2013


TDUV Time Setting for IB4
[IB 4 TDUV Time]
Parameter Number:

136,116,_,_,_.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-4-50

Group:

Configuration

Units:

Seconds error in EDS file

Minimum Value:

0.2

Maximum Value:

2.0

Default Value:

0.2

This parameter allows the user to view and set the Time Delay

Undervoltage setting for the IB4 module. The Time Delay

Undervoltage setting is the time allowed for contactor IB4 to remain

operational when the mains input voltage goes below the minimum

operating voltage (see Electrical Specifications section for both

Close and Hold modes). See TDUV Programmability in Chapter 4

for a detailed description of this feature.


TDUV Time Setting for IB5
[IB 5 TDUV Time]

Parameter Number:

137,_,_,_,_.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-5-50

Group:

Configuration

Units:

Seconds error in EDS file

Minimum Value:

0.2

Maximum Value:

2.0

Default Value:

0.2

This parameter allows the user to view and set the Time Delay

Undervoltage setting for the IB5 module. The Time Delay

Undervoltage setting is the time allowed for contactor IB5 to remain

operational when the mains input voltage goes below the minimum

operating voltage (see Electrical Specifications section for both

Close and Hold modes). See TDUV Programmability in Chapter 4

for a detailed description of this feature.