Parameters B-77

1503-UM054C-EN-P – June 2013

Delay Restart Time for IB3
[IB 3 Delay Restart Time]

Parameter Number:

140,119,98,_,_.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-3-19

Group:

Configuration

Units:

Seconds

Minimum Value:

6

Maximum Value:

3600

Default Value:

12

This parameter allows the user to view and set the Delay Restart

Time between successive Open/Trip and Close commands for

contactor IB3. This sets a maximum repetition time for the cycling

of the contactor. It can also be used to prevent rapid restating of the

motor. See Delayed Restart in Chapter 4 for a more detailed

description of this feature.

Delay Restart Time for IB4
[IB 4 Delay Restart Time]
Parameter Number:

141,120,_,_,_.

Access rule:

Get/Set

Data Type:

UINT

Object Mapping:

0x384-4-19

Group:

Configuration

Units:

Seconds

Minimum Value:

6

Maximum Value:

3600

Default Value:

12

This parameter allows the user to view and set the Delay Restart

Time between successive Open/Trip and Close commands for

contactor IB4. This sets a maximum repetition time for the cycling

of the contactor. It can also be used to prevent rapid restating of the

motor. See Delayed Restart in Chapter 4 for a more detailed

description of this feature.