Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 162

Advertising
background image

DeviceLogix 9-39

1503-UM054C-EN-P – June 2013

After selecting the desired control program the IntelliVAC Plus

module must be reset to adopt its new settings and load the logic

from main memory into the DeviceLogix engine. In order to

accomplish this simply cycle the control power of the unit. Be sure

to remove both the 120VAC power to the IntelliVAC module, and

the 24VDC DeviceNet power.

When power is restored to the IntelliVAC Plus the new program will

be active in DeviceLogix. In order to view the logic in RS-Networx

you must delete the IntelliVAC Plus icon from the network view and

perform a scan of the network in order to obtain the new settings.

Note

: In order for pre programmed logic to function correctly the

hardware inputs to the IntelliVAC Plus MUST be wired

according to the Multi contactor wiring guide of Chapter 6.


Note

: Only timer values may be changed in pre programmed

program. If any other changes are required the user must use

the “User Customized Logic” option. The logic is ready only

in Firmware. If modification or forced I/O value in

DeviceLogix editor and error message will pop up. The only

changeable attribute is the timer’s preset value.


Note

: The following conditions must be met in order to change a

pre configured logic block.

I M P O R T A N T

I M P O R T A N T

The system must be running free of faults or

warnings.

All Hardware inputs on the Plus module must

be “0” or all HW inputs on the module must be

disconnected.

All contactors must be OPEN and the

DeviceLogix engine must be in the “stopped’

state

The IE module must be configured for the

appropriate number of contactors, see
Configuration

.

The “DeviceLogix” control mask must be

selected.