Explicit connection – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 369

E-4
DeviceNet Information
1503-UM054C-EN-P – June 2013
Explicit Connection
Table E.9 - Instance Attributes (predefined slave explicit connection)
Attribute
ID
Access
Rule
Attribute Name
Data
Type
Data Value
1
Get
state
USINT
0=nonexistent
1=configured
3=established
4=time out
2
Get
instance_type
USINT
0=explicit message
3
Get
transportClass_trigger
BYTE
83hex, server, transport
class 3
4
Get
produced_connection_id
CAN header field 11 bit message
UINT
10xxxxxx011
xxxxxx=node address
5
Get
consumed_connection_id
CAN header field 11 bit message
UINT
10xxxxxx100
xxxxxx=node address
6
Get
initial_comm._characteristics
USINT
21hex
2=slave’s explicit message
(produce, source)
1=master’s explicit request
(consume, destination)
7
Get
produced_connection_size
UINT
Max. 132
8
Get
consumed_connection_size
UINT
Max. 132
9
Get/Set
expected_packet_rate
UINT
2500 ms (default), with
timer resolution of 10 ms
12
Get/Set
watchdog_timeout_action
USINT
1=auto delete
3=defer delete
13
Get
produced_connection_path_length
USINT
0
14
Get
produced_connction_path
EPATH Null
15
Get
consumed_connection_path_length
UINT
0
16
Get
consumed_conection_path
EPATH Null