Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 256

Advertising
background image

Parameters B-81

1503-UM054C-EN-P – June 2013


Jog Time for IB1 [IB 1 Jog Time]

Parameter Number:

148,125,102,79,55.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-1-21

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

30

Default Value:

12

This parameter allows the user to view and set the Jog Time for

contactor IB1. It indicates the amount of time that a contactor can be

Jogged (momentarily closed) for. This is only for Electrically Held

contactors and makes use of the Open command. See Temporary

Jog Function in Chapter 4 for a more detailed description of this

feature.


Jog Time for IB2 [IB 2 Jog Time]

Parameter Number:

149,126,103,80,_.

Access rule:

Get/Set

Data Type:

USINT

Object Mapping:

0x384-2-21

Group:

Configuration

Units:

Seconds

Minimum Value:

0

Maximum Value:

30

Default Value:

12

This parameter allows the user to view and set the Jog Time for

contactor IB2. It indicates the amount of time that a contactor can be

Jogged (momentarily closed) for. This is only for Electrically Held

contactors and makes use of the Open command. See Temporary

Jog Function in Chapter 4 for a more detailed description of this

feature.