IntelliVAC Plus Basic Wiring 5-9

1503-UM054C-EN-P – June 2013

MOV

3

2

1

EC

-

+

4

TCO

12

11

AUX

CCO

5

6

L1

L2/N

G

+ -

CLOSE

OVERLOAD

CONTROL

POWER

FUSE

*

CONTROL POWER

M-IV

9

10

CLOSE

CC

M-IV

M

MOV

TC

M

+ -

M-IV

7

8

OPEN

OPEN

CAPACITOR

OVERLOAD

*

Refer to Table 3.A for recommended fuse sizing.

Figure 5.7 – Mechanical Latch Contactor with Capacitor Trip Option


Time Delay Undervoltage

The IntelliVAC can be configured to provide time delay undervoltage

(TDUV) protection. The feature is available to keep electrically held

contactors closed during a voltage dip or brief power loss. This

option may require the addition of a capacitor (see Table 5.D). Refer

to Table 5.E for typical capacitor sizing. The capacitor is connected

to terminals 1(-) and 2(+) of the IntelliVAC. (Refer to Figure 5.8)

A T T E N T I O N

A T T E N T I O N

If the TDUV feature is used, the contactor

will not open until the programmed TDUV

time has expired. Therefore, applications

requiring an immediate removal of power

during emergency stop conditions are not

compatible with the TDUV feature.

Table 8.E of the “Configuration/Programming” Chapter 8 has the

DIP switch settings to provide TDUV from 0.2 to 2 seconds.

IntelliVAC can provide TDUV protection without the use of an

external capacitor, as shown in Table 5.D.