Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 216

Advertising
background image

Parameters B-41

1503-UM054C-EN-P – June 2013


Discrete Output Point Idle Value [DOP Idle Value]

Parameter Number:

75,63,51,34,26.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0x1E-1-10

Group:

Control

Units:

-

Minimum Value:

0 = Off

Maximum Value:

1 = On

Default Value:

0

Dictates if any extra action will be performed on the existence of a

DOP idle condition.

Communication Parameters

DeviceNet Baud Rate [DNet Baudrate]

Parameter Number:

76,64,52,40,27.

Access rule:

Get/Set

Data Type:

SINT

Object Mapping:

0x3-1-2

Group:

Communication

Units:

-

Minimum Value:

0 = 125K

Maximum Value:

2 = 500K

Default Value:

2

This parameter allows the user to view and set the baud rate of the

DeviceNet communications network.

For each of the Baud Rate Values listed, the corresponding Baud

Rate is indicated.

Table B11 – DeviceNet Band Rate

Value

Enum Text

Description

0

125 K

Baud Rate set to 125K

1

250 K

Baud Rate set to 250K

2

500 K

Baud Rate set to 500K