Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 243

Advertising
background image

B-68

Parameters

1503-UM054C-EN-P – June 2013

Table B.27 – Drop Out Time Settings From IB5 DIP Switches

Value

Enum Text

Description

0

50 ms

50 ms from IB5 DIP switches

1

75 ms

75 ms from IB5 DIP switches

2

100 ms

100 ms from IB5 DIP switches

3

130 ms

130 ms from IB5 DIP switches

4

150 ms

150 ms from IB5 DIP switches

5

175 ms

175 ms from IB5 DIP switches

6

200 ms

200 ms from IB5 DIP switches

7

240 ms

240 ms from IB5 DIP switches


Contactor Pick Up Time for IB1
[IB 1 Pick Up Time]

Parameter Number:

123,105,87,69,50.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-1-18

Group:

Configuration

Units:

mSeconds

Minimum Value:

0

Maximum Value:

255

Default Value:

0

This parameter allows the user to view the Pick Up Time for the IB1

contactor. The Pick Up Time is the interval from when a Close or

Trip command is issued to the time that the Contactor Auxiliary

contact on IB1 opens, indicating that the contactor is closed.


Contactor Pick Up Time for IB2
[IB 2 Pick Up Time]

Parameter Number:

124,106,88,70,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-2-18

Group:

Configuration

Units:

mSeconds

Minimum Value:

0

Maximum Value:

255

Default Value:

0

This parameter allows the user to view the Pick Up Time for the IB2

contactor. The Pick-Up Time is the interval from when a Close or

Trip command is issued to the time that the Contactor Auxiliary

contact on IB2 opens, indicating that the contactor is closed.