Anti-kiss, Anti-pumping, Re-closing control features – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 32

Advertising
background image

Description of Features 4-5

1503-UM054C-EN-P – June 2013

Time. If the contactor did not close within 200mS then there is a

major problem and it probably would not pick up any time after that.

A contactor should, if it does not have any mechanical or electrical

problems, close within 150mS. If a contactor requires longer than

150mS to close, then this is a sign that it is beginning to have problems.

This condition, although it does not cause any faults or warnings,

will be logged to the Event Log (see Event Log in Chapter 4).
To determine component wear of the contactor over its lifetime, the

close time will be monitored as a wear indicator. To perform this

measurement the close time will be averaged over the last 5 closures

and when the present value has exceeded the table value threshold,

then, an extended close time alarm will be annunciated. See Table

4.F – Plus Fault/Warning Description for the warning description

and Table 4.G – Contactor Extended Close Times for limits which

define an extended close time.

Anti-Kiss

The IntelliVAC Plus has an anti-kiss protection feature. This feature

will ensure that the main contacts are closed and sealed before they

are allowed to open. The IntelliVAC Plus makes all decisions on

whether to open or close the contactor. Once a contactor has been

commanded to close, it cannot be commanded to open until it has

actually closed first. To determine if the contactor has actually

closed, it monitors the contactor Auxiliary input at terminals TB

11/12 (see table 5.B). The IntelliVAC Plus will wait for a ‘contactor

closed’ status before issuing an open command, assuming that an

active open command has become issued shortly after a close

command has been issued. Open and close commands are also

available from the DeviceNet network as status bits (see Appendix E

for details). The basic rule for this feature is that the removal of the

Close command must have at least a 200mS delay from the time that

a Close command was initiated, even if the Auxiliary status indicates

that the contactor has closed before the 200mS time.

Anti-Pumping

Anti-pumping protection is intended to prevent the contactor from

rapid open-close cycling due to an inappropriate or faulty control

circuit, a faulty holding coil or control electronics, or the failure of a

latch mechanism to engage.

The input control signal is required to toggle before issuing another

close command. If the contactor receives a signal to close, and the

contactor closes, but immediately opens, the close command will be

ignored unless the close command is removed and re-applied.

Re-Closing Control

Features

Advertising