Description of Features 4-45

1503-UM054C-EN-P – June 2013

For the 7-segment LED display, the ‘Watchdog Timeout’ and the

‘System Lock-Out State’ will have the highest priority with the

‘Watchdog Timeout’ being the higher of the two.

If there are multiple MC faults, then the highest MC fault, only, will

be displayed on the 7-segment display.

Note

: See Figure 4.1 for the 7-segment LED display

Note that all of the Fault codes displayed on the 7-segment LED
display refer to RS485 errors or fatal errors where the display
would no longer be useful for displaying address information.

RS485 Incorrect/Duplicate Addresses

This is a Fault condition and indicates that the IntelliVAC MC

system has IntelliVAC MC units with incorrect and/or duplicate

RS485 addresses. The MC address for the individual units must be

changed using the DIP switches on the IntelliVAC MC module (see

Table 8.H and figure 8.2). The RS485 addresses must contain only

the addresses up to and including the maximum number of units in

the MC system. For example, in an MC system with three units,

there must only be addresses ‘2’ and ‘3’ selected by the two

IntelliVAC MC modules, as address 1 is already defined by the

IntelliVAC Plus unit. If addresses ‘2’ and ‘2’ are selected

(duplicated addresses) or addresses ‘2’ and ‘4’ (incorrect addresses)

are selected then this Fault code will be displayed.
The 7-segment display will display the solid character ‘-1’.

Table 4.J – 7-Segment LED Display Fault Codes

FAULT/WARNING

SEGMENT

MODE

DESCRIPTION

a

b

c

d

e

f

g

DP

RS485 Incorrect/Duplicate Addresses

Off On On

Off

Off Off On

Off

Solid

‘-1’

MCC Bad MC #1

Off On On

Off

Off Off

Off

Off

Flash

‘1’

MCC Bad MC #2

On On Off On On Off On

Off

Flash

‘2’

MCC Bad MC #3

On On On On

Off Off On

Off

Flash

‘3’

MCC Bad MC #4

Off On On

Off

Off On On

Off

Flash

‘4’

MCC Bad MC #5

On

Off On On

Off On On

Off

Flash

‘5’

Incorrect MCC R

TERM

Installed

Off

Off On On On On On

Off

Flash

‘6’

System Lock-Out State

On On On

Off

Off Off

Off

Off

Flash

‘L’ + MC address ‘1’

Bad/no DeviceLogix Prog for MC

System

On On On On

Off Off On

Off

Solid

‘3’

Lost +15V Rail From IB1

On On On

Off

Off Off

Off

On

Flash

‘7+DP’

Watchdog Timeout – Fatal Error (NMI) On On On On On On On

On

Flash

‘8+DP’