Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 186

Advertising
background image

Parameters B-11

1503-UM054C-EN-P – June 2013


Close Coil Command for IntelliVAC Base Unit #1
[IB 1 Close Coil Command]
Parameter Number:

16,13,10,7,4.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0x384-1-4

Group:

Control

Units:

-

Minimum Value:

0 = Off

Maximum Value:

1 = On

Default Value:

0

This parameter allows the user to view as well as change the Close

Coil command for the IntelliVAC Basic Module #1. An Off refers to

the Close command not being present and not applying power to the

Close coil. An On refers to the Close command being present and

applying power to the Close coil.


Close Coil Command for IntelliVAC Base Unit #2
[IB 2 Close Coil Command]

Parameter Number:

17,14,11,8,_.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0x384-2-4

Group:

Control

Units:

-

Minimum Value:

0 = Off

Maximum Value:

1 = On

Default Value:

0

This parameter allows the user to view as well as change the Close

Coil command for the IntelliVAC Basic Module #2. An Off refers to

the Close command not being present and not applying power to the

Close coil. An On refers to the Close command being present and

applying power to the Close coil.