Troubleshooting

IB Operational Troubleshooting Procedures

The following table identifies possible causes and corrective actions

when troubleshooting IB related faults using the IntelliVAC Plus

Module Status/Contactor Status LEDs.


NOTE:

All parameters indicated in this section refer to a 5IB-MC

system. See the appropriate section of Appendix B for the

corresponding parameter for other IB-MC version.

Table 10.A – IB Operational Troubleshooting Procedures

LED Color

State

Condition/Possible Cause

Corrective Action

Module

Status

Contactor

Status

Green

Off

Normal

The module is healthy and the contactor is

open.

No action required.

Green

Yellow

Normal

The module is healthy and the contactor is

closed.

No action required

Yellow

Off

Warning

An invalid command was present
The Close, Jog or Trip commands were

present during a power up

sequence.

The Close or Jog command was re-

applied too quickly (before the

contactor opening sequence is

verified)





The Close and Trip commands are

present simultaneously (only valid

for Mechanical Latch contactors)

Prevent Close, Jog or Trip commands

from being present during a power up

sequence.

The Close command can only be re-

applied as described in the Delayed

Restart section. Increase the delay time

between removal of the Close command

and its reapplication.

The Jog command can only be reapplied

as described in the Temporary Jog

Function section. Increase the delay time

between removal of the Jog command

and its reapplication.
Prevent the Close and Trip commands

from simultaneously being applied. The

Trip command can only be applied within

a minimum of 200mS from the application

of the Close command.