Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 196

Parameters B-21
1503-UM054C-EN-P – June 2013
Close Coil Current for IntelliVAC Base Unit #1
[IB 1 Close Current]
Parameter Number:
36,29,22,15,8.
Access rule:
Get
Data Type:
FLOAT
Object Mapping:
0x384-1-8
Group:
Control
Units:
Amperes
Minimum Value:
00.000A
Maximum Value:
99.999A
Default Value:
00.000A
This parameter allows the user to view the average value for the
Close coil current on the IntelliVAC Basic Module #1. This coil
current is only valid for the first 200mS after the Close coil is
energized.
Close Coil Current for IntelliVAC Base Unit #2
[IB 2 Close Current]
Parameter Number:
37,30,23,16,_.
Access rule:
Get
Data Type:
FLOAT
Object Mapping:
0x384-2-8
Group:
Control
Units:
Amperes
Minimum Value:
00.000A
Maximum Value:
99.999A
Default Value:
00.000A
This parameter allows the user to view the average value for the
Close coil current on the IntelliVAC Basic Module #2. This coil
current is only valid for the first 200mS after the Close coil is
energized.