MC RS485 Addressing

This set of DIP switches defines the RS485 address of the

IntelliVAC MC unit(s) within an MC system.

Table 8.H – MC RS485 Address Settings

MC Address

DIP S1

Description

1

2

3

0

OFF

OFF

OFF Not allowed – allocated to Advanced Module

1

OFF

OFF

ON

Not allowed – allocated to IB1 module

2

OFF

ON

OFF

Valid MC Address

3

OFF

ON

ON

Valid MC Address

4

ON

OFF

OFF

Valid MC Address

5

ON

OFF

ON

Valid MC Address

6

ON

ON

OFF

Invalid MC Address

7

ON

ON

ON

Invalid MC Address

RS485 Termination Resistor

This one DIP switch defines whether a termination resistor will be

inserted between the RS485A and RS485B differential data lines on

the particular IntelliVAC MC unit. It is used only on the IntelliVAC

MC module with the highest address in an MC system. This resistor

provides a load for the transmitter such that there are no reflections

of the transmitted signal. In effect the termination resistor provides

the load with a received signal which is a duplicate of the transmitted

signal, with no distortion.

Table 8.J – RS485 Termination Resistor Configuration

R

TERMINATION

DIP S1

6

Termination resistor not inserted

OFF

Termination resistor inserted

ON


A T T E N T I O N

A T T E N T I O N

In an MC system the termination resistor must

be installed in the IntelliVAC MC unit with the

highest address, only. If the correct termination

resistor is not installed, then an ‘Incorrect MC

RTERM Installed’ fault will be displayed on

the 7-segment LED display. (See

Troubleshooting Procedures in Chapter 10).