Mechanical latch contactors – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 83

Advertising
background image

5-8

IntelliVAC Plus Basic Wiring

1503-UM054C-EN-P – June 2013

Capacitor Trip

The IntelliVAC can be configured to provide capacitor trip

functionality with mechanical latch contactors. A capacitor must be

connected to the IntelliVAC (terminals #1 and #2) in order to

provide this capability. The capacitor provides control power for the

IntelliVAC as well as stored energy to trip the contactor. Maximum

recommended capacitor size is 1650 µF for 120V control or 330 µF

for 240V control. Use of larger capacitors will require a current

limiting circuit to prevent opening the control fuse on energization.

The IntelliVAC must receive an ‘OPEN’ command within a few

seconds of losing AC control power. This time limit depends on

voltage and capacitor size as shown in the table below. If the elapsed

time exceeds this limit, the contactor cannot be tripped by

IntelliVAC. In this case, the contactor can be tripped by pressing the

release button on the door in front of the contactor.

A separate voltage source is needed to provide the ‘OPEN’ command.

This may be taken from the external capacitor as shown in Figure

5.7.

Table 5.C – Mechanical Latch Contactor – Capacitor Trip Times

Contactor

Rating

Nominal Voltage

(Vac)

Actual

V

input

(Vac)

Ext.

Capacitor

(µF)

Max. time

for trip

(sec)

400 Amp

120

120

1650

3.5

110

2.7

100

1.7

240

240

330

7.5

200

4.7

Note:

Minimum capacitor voltage ratings:

• 120V applications – 200V DC (250V DC preferred)

• 240V applications – 400V DC (450V DC preferred)

Mechanical Latch

Contactors

Advertising