Troubleshooting 10-3

1503-UM054C-EN-P – June 2013


Table 10.A – IB Operational Troubleshooting Procedures (cont.)

LED Color

State

Condition/Possible Cause

Corrective Action

Module

Status

Contactor

Status

Yellow -

Red

3 flash

Off/Yellow

(depends

on status

of

contactor)

Warning

Long contactor drop out time
Contactor Auxiliary status missing

Faulty contactor coil
Faulty vacuum bottles

Check that the Contactor Auxiliary status

connection between the contactor and

TB11/1,2 on the IntelliVAC Plus is correct.
Check the condition of the main contactor

coil.
Check the mechanical condition of the

vacuum bottles.

Red

Red

Fault

Microcontroller malfunction
Low input mains voltage


Faulty IntelliVAC Plus

Check that the IntelliVAC Plus input

voltage is greater than or equal to the

minimum level listed in the Electrical

Specifications section. Recycle the input

power, as well as the DeviceNet power, if

present.
Replace the IntelliVAC Plus unit.

Red

1 flash

Off

Fault

Power up with invalid DIP switch

configuration
DIP switches set incorrectly

1. The SW1/SW2 DIP switches are set.

See DIP switch configuration and

confirm that it is correct for the

contactor being controlled.

Red

3 flash

Red

Fault

Contactor fails to drop out

1. Contactor Auxiliary status missing

2. Contactor Auxiliary status contact

bad

3. Faulty vacuum bottles

4. Obstruction in contactor


Check that the Contactor Auxiliary status

connection between the contactor and

TB11/1,2 on the IntelliVAC Plus is correct.
Check that the contactor Auxiliary status

contacts are functioning.
Check that the contactor bottles are not

welded closed.
Check that there is not an obstruction (or

possible binding in the contactor pivot

points) in the contactor which prevents

the bottle armature from opening.

Red

4 flash

Off

Fault

RS 485 communications error
Application jumper incorrectly installed

Enhanced module in reset state

RS485 cables missing/bad

1. Check that the Enhanced module

Application Disable jumper (JP3) is in

position 2-3 and not in position 1-2.

2. Check that the Plus Status LED is not

solid red (Advanced module has a

microcontroller malfunction).

3. In an MC system check that the RS485

cable connection s between all of the

modules is correct.

Red

4 flash

Off

Fault

Application jumper incorrectly installed in

other MC units

4. In an MC system check that the

IntelliVAC MC units programming

jumpers (JP1) are in position 2-3 and

not in position 1-2.