Parameter numbers, Control parameters – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 178

Advertising
background image

Parameters B-3

1503-UM054C-EN-P – June 2013

Table B.3 – Conversion Table

Binary

Hex

Binary

Hex

Binary

Hex

Binary

Hex

0000

0

0100

4

1000

8

1100

C

0001

1

0101

5

1001

9

1101

D

0010

2

0110

6

1010

A

1110

E

0011

3

0111

7

1011

B

1111

F

Parameter Numbers

The parameter number value, for each parameter type, lists 5 values

separated by commas. The description of these 5 values is as

follows:

a, b, c, d, e

a = parameter number for a 5IB multi-contactor system

b = parameter number for a 4IB multi-contactor system
c = parameter number for a 3IB multi-contactor system

d = parameter number for a 2IB multi-contactor system

e = parameter number for a 1IB multi-contactor system

Depending on the multi-contactor system which is used, simply

select the value of the parameter number corresponding to the

appropriate system.


Control Parameters

Auxiliary Input Status from IntelliVAC Base Unit #1
[IB 1 Module Aux. Status]

Parameter Number:

1,1,1,1,1.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-1-1

Group:

Control

Units:

-

Minimum Value:

0 = Closed

Maximum Value:

1 = Open

Default Value:

0

This parameter allows the user to view the status of the contactor

Auxiliary input from the IntelliVAC Basic Module #1. A Closed

status refers to the contactor Auxiliary input having no input voltage

which indicates that the contactor is Closed. An Open status refers to

the contactor Auxiliary input having a valid input voltage which

indicates that the contactor is Open. See the Electrical Specifications

section in Table 1.A for the voltage level for a valid Closed and

Open input.