Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 232

Advertising
background image

Parameters B-57

1503-UM054C-EN-P – June 2013


Time Delay UnderVoltage Setting for IB5
[IB 5 TDUV Configure]
Parameter Number:

102,_,_,_,_.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0x384-5-15

Group:

Configuration

Units:

-

Minimum Value:

0 = Disable

Maximum Value:

1 = Enable

Default Value:

0

This parameter allows the user to view and set the status of the Time

Delay UnderVoltage setting for the IB5 contactor module. If it is

disabled then the TDUV feature for the IB5 contactor is disabled. If

it is enabled then the TDUV feature for the IB5 contactor is enabled.

See TDUV in Chapter 8 and Table 8.D.

Power-Up Safety Setting for IB1
[IB 1 Power-Up Safety Setting]

Parameter Number:

103,89,75,61,46.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-1-16

Group:

Configuration

Units:

-

Minimum Value:

0 = Enable

Maximum Value:

1 = Disable

Default Value:

0

This parameter allows the user to view the status of the Power-Up

Safety setting for the IB1 module. If it is enabled then the IB1

contactor will not close the contactor if the unit powers up with a

Close command present. If it is disabled then the IB1 contactor will

close the contactor if the unit powers up with a Close command

present. See Power-up Safety in Chapter 8 and Table 8.F.