Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 62

Advertising
background image

Description of Features 4-35

1503-UM054C-EN-P – June 2013

Programming Base Unit(s)

This is a Normal firmware flashing condition and no additional

action is required.

The Basic module is in the process of being flashed from a PC over

the RS485 communications link. The data rate for this process is

9600 baud. See Chapter 8 for Firmware Flashing.

The Plus status LED is flashing Green at a 0.50Hz rate so that the

LED is on for 1 second, then off for 1 second and then it repeats.

No Power from IB or DeviceNet

This is a Normal condition if there are no input power sources to the

IntelliVAC Plus module. If this condition exists and there is at least

one source of external power supplied to the IntelliVAC Plus unit

then a serious problem may exist. Refer all servicing for qualified

service personnel or see the trouble shooting section in Chapter 10.

The Advanced module has no power from either the Basic module or

from DeviceNet.

The causes of the loss of Basic module power are either that there is

no 120/240V mains input power to the IntelliVAC Plus module or

that this input voltage is <50Vrms. Also, the internal DC power

source on the Basic module has failed or the internal DC power

source on the Advanced module has failed, or both. Also, there is no

DeviceNet power or the internal DC power source of the Advanced

module has failed.

The IntelliVAC Plus status LED is off.

RTC Fail

This is a Warning condition which may not be rectified by the user.

Refer all servicing to qualified service personnel, or see the trouble

shooting section in Chapter 10.

The Real Time Clock circuitry is not responding which will prevent

the Event Log (see Event Log in Chapter 4) from time stamping

events with the correct local time.

The Plus status LED is pulsing Green with a pattern of 2 pulses.