Chapter

5

1503-UM054C-EN-P – June 2013

IntelliVAC Plus Basic Wiring


Fuse Protection

The IntelliVAC module requires external fuse protection to

coordinate with the power supply and contactor. The fuse ratings

shown in Table 5.A allow the passage of inrush currents expected

when the contactor is closed, or from recommended external

capacitors for the TDUV option. They will also protect the contactor

coils in the event of a module malfunction.

The recommended fuses have been tested to ensure reliable

protection of the module. If the supply voltage is DC, the module

must be used with an external fuse that is approved for and rated to

interrupt the DC voltage supply. The types listed are Ferraz-Shawmut

Midget Fuses (1-1/2" X 13/32"). The TRM is a time-delay type,

rated 250 VAC. The ATM is a fast-acting type, rated 500 VDC.

Table 5.A – IntelliVAC Plus Fuse Protection

Rated Supply Voltage

Contactor Type

Recommended Fuse

(minimum)

(maximum)

110/120 VAC

400A EH

TRM 2

TRM 3.2

800A EH

TRM 2

TRM 6.25

400/800A ML

TRM 2

TRM 3.2

220/240 VAC

400A EH

TRM 2

TRM 6.25

800A EH

TRM 2

TRM 6.25

400/800A ML

TRM 2

TRM 6.25

125 VDC

400A EH/ML

ATM 3

ATM 3

800A EH/ML

ATM 5

ATM 6

250 VDC

400A EH/ML

ATM 3

ATM 5

800A EH/ML

ATM 5

ATM 6

EH = Electrically Held vacuum contactor

ML = Mechanical Latch vacuum contactor

Note:

If external capacitors are connected, or more than one

IntelliVAC module is protected by a common control fuse,

the maximum recommended fuse should be used to

prevent fuse opening due to increased inrush current when

control power is applied.

IntelliVAC Base

Wiring