Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 240

Advertising
background image

Parameters B-65

1503-UM054C-EN-P – June 2013

Drop Out Time Setting From IB1 DIP Switches
[IB 1 Drop Out Time DIP Setting]

Parameter Number:

118,101,84,67,49.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-1-49

Group:

Configuration

Units:

milliseconds

Minimum Value:

0

Maximum Value:

7

Default Value:

0

This parameter allows the user to view the Drop Out Time Setting

set from the IB1 DIP switches. The Drop Out Time is initially set by

the IB1 DIP switches but can be over-ridden by Parameter #113 after

which time the original IB1 DIP switch settings will no longer be

used.

Table B.23 – Drop Out Time Settings From IB1 DIP Switches

Value

Enum Text

Description

0

50 ms

50 ms from IB1 DIP switches

1

75 ms

75 ms from IB1 DIP switches

2

100 ms

100 ms from IB1 DIP switches

3

130 ms

130 ms from IB1 DIP switches

4

150 ms

150 ms from IB1 DIP switches

5

175 ms

175 ms from IB1 DIP switches

6

200 ms

200 ms from IB1 DIP switches

7

240 ms

240 ms from IB1 DIP switches


Drop Out Time Setting From IB2 DIP Switches
[IB 2 Drop Out Time DIP Setting]

Parameter Number:

119,102.85,68,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-2-49

Group:

Configuration

Units:

see table

Minimum Value:

0

Maximum Value:

7

Default Value:

0

This parameter allows the user to view the Drop Out Time Setting

set from the IB2 DIP switches. The Drop Out Time is initially set by

the IB2 DIP switches but can be over-ridden by Parameter #114 after

which time the original IB2 DIP switch settings will no longer be

used.