Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 287

Advertising
background image

B-112

Parameters

1503-UM054C-EN-P – June 2013


Module not Healthy on IB3 [IB 3 Module not Healthy]

Parameter Number:

210,175,140,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-3-28

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of the Module not

Healthy fault

from the IB3 module. If the bit is ‘0’ then the warning

is not present. If the bit is ‘1’ then the warning is present. See Table

4.E and related description for a detailed description of this warning.


Module not Healthy on IB4 [IB 4 Module not Healthy]

Parameter Number:

211,176,_,_,_.

Access rule:

Get

Data Type:

BOOL

Object Mapping:

0x384-4-28

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Not Present

Maximum Value:

1 = Present

Default Value:

0

This parameter allows the user to view the status of the Module not

Healthy fault from the IB4 module. If the bit is ‘0’ then the warning

is not present. If the bit is ‘1’ then the warning is present. See Table

4.E and related description for a detailed description of this warning.